Product Details:
Payment & Shipping Terms:
|
Usage: | Current | Phase: | Single |
---|---|---|---|
Coil Structure: | Toroidal | Coil Number: | Autotransformer |
High Light: | Current Clamp Sensor,high precision current clamp adapter,Clamp on Power Sensor |
Application
power quality measuring
Large industrial load
HVAC
measuring around cable bundles
power load monitoring
waveform analysis
Features
measurement range: 1mA--3000A
small, compact size
conform to EN 61010, 600V CAT three
low phase shift for power measurement
Designed for DMMs, recorders, loggers, oscilloscopes, power and harmonic meters
Output model: Lead output(2.5m)
Specifications
Electrical parameters | |
---|---|
Ratio | 1000: 1 or 2000:1 (customized) |
Accuracy class | 0.2%, 0.5% |
Primary current | 0 - 3000A AC |
Secondary current | 0 - 5A AC (customized) |
Max. Cont. Input current | 3600A |
Over voltage category | CAT III 600 V |
Output signal | 500mA,1A,5A AC at nominal input current |
Frequency range | 40Hz-2000Hz |
Dielectric strength | 3KV 50Hz/60Hz at 1 minute |
Temperature range | -20°C to +55°C |
Output | 2.5 meter cable with D01 connector |
Max. voltage not insulated conductors | 600 V |
Standard | EN 61010-1, EN 61010-2-032 |
Installation | clamp type |
Output mode | lead output(2.5m) |
Mechanical parameters | |
Dimensions (L x W x H) (mm) | 116 x 327 x 35 |
Weight (g) | 1200 |
Holding wire diameter (mm) | φ120 x 50 |
Max. jaw opening (mm) | 50 |