Product Details:
Payment & Shipping Terms:
|
Highlight: | digital power meter,ethernet power meter,power meter data logger |
---|
Mini multifunction stop data logger Ethernet digital power meter
FU2200A Description
FU2200A Three Phase Multi-function digital Ethernet power meter with data logger is a range of economical yet highly functional three-phase multifunction power and energy meters manufactured by GFUVE.
FU2200A three phase power recorder meter provide excellent value for monitoring power and energy management systems. The Ethernet power meter can be used as data gathering devices for intelligent power distribution or plant automation systems. All monitored data is available via a standard digital RS485 communication port running the Modbus RTU protocol. With a wide range of models to choose from, FU2200A Three Phase Multi-function digital Ethernet power meter with data logger offers unparalleled value and functionality.
Features
True-RMS measuring Parameters.
ANSI and IEC 0.5 Accuracy class.
Power Quality Analysis.
4 Quadrant Energy;
4MB onboard memory;
Data logging
High-speed RS485, Ethernet Port (optional);
Measure Individual Harmonics from 2nd to 63th (optional);
Module Design;
TOU, 4 Tariffs, 12 Seasons, 14 Schedules
Class leading Warranty.
With management software
Applications
Metering of distribution feeders, transformers, generators, capacitor banks and motors.
Medium and low voltage systems.
Commercial, industrial, utility.
Power quality analysis.
Specifications
Parameter | Accuracy | Resolution | Range | |
Voltage | 0.2% | 0.01V | 0.5-500kV | |
Current | 0.2% | 0.01mA | 5mA-50000A | |
Active Power | 0.5% | 0.2W | -9999MW to +9999MW | |
Reactive Power | 2% | 0.2var | -9999Mvar to +9999Mvar | |
Apparent Power | 0.5% | 0.2VA | 0-9999MVA | |
Active Power Demand | 0.5% | 0.2W | -9999MW to +9999MW | |
Reactive Power Demand | 2% | 0.2var | -9999Mvar to +9999Mvar | |
Apparent Power Demand | 0.5% | 0.2VA | 0-9999MVA | |
Power Factor | 0.005 | 0.0001 | -1.0000-0-1.0000 | |
Frequency | 0.01Hz | 0.01Hz | 45.000-65.000Hz | |
Energy | Primary | 0.5% | 0.1kWh | 0-99999999.9kWh |
Secondary | 0.001kWh | 0-999999.999kWh | ||
Reactive Energy | Primary | 2% | 0.1kvarh | 0-99999999.9kvarh |
Secondary | 0.001kvarh | 0-999999.999kvarh | ||
Apparent Energy | Primary | 0.5% | 0.1VAh | 0-99999999.9kVAh |
Secondary | 0.001VAh | 0-999999.999kVAh | ||
Phase Angle | 0.1° | 0.01° | 0-359.99° | |
Unbalance Factor | 2% | 0.01% | 0-300.00% | |
PT | 1 | 1-10000 | ||
CT | 1 | 1-10000 | ||
Addr | 1 | 1-254 |
Current Input
Rated Current 5A/1A ac
Measurement Range: 0-6A ac
Overload capacity 20A continuous, 50A 10Sec, 100A 1Sec
Burden: 0.5VA @5A RMS
Current start 0.1%Rated value
Accuracy 0.2%
Voltage Input
Rated voltage 400Vac L-N, 690Vac L-L
Input Impedance 1MΩ per phase
Overload capacity 1500Vac continuous,2500Vac 50/60Hz 1min
Frequency: 45Hz-65Hz
Accuracy 0.2%
Energy Accuracy
Active class 0.5S (IEC62053-22,GB/T17215.322-2008)
Reactive class 2 (IEC62053-23)
Power Supply (AC/DC)
Range: 85-265Vac,50/60Hz;100-300Vdc
Power Consumption: 5W
Insulation voltage capacity2000Vac,50/60Hz,1min
FU2200A Photos