Product Details:
Payment & Shipping Terms:
|
High Light: | Panel Power Analyzer,3 Phase Harmonics Power Analyzer,Harmonics Analyzer |
---|
Introduction
FU2200A is amultifunctionpower analyzer, It can measure all the electric parameters in the circuit, and it has RTC, calendar and one pulse output.
Measurement Parameters
Voltage (Ph-N);Voltage (Ph-Ph);Current;Frequency;PF;Active Power(W);Reactive Power(Q);
Apparent Power(S)
Computation
Forwardactive power energy
Reverse activepower energy
Forward active power energy
Reverse reactive power energy
Measuring Range
30-600V, 0-6A, 45-65Hz, -1-0-1
Measuring Accuracy
Frequency | 0.10% |
Electric energy | 0.5%, 1.0% |
Voltage | 0.2%±0.1V |
Current | 0.2%±0.001A |
Power | 0.5% ±0.4W |
Power Factor | 0.5% ±0.001 |
Display
LCD Display,128´64 Lattice, English and Chinese interface, 4Displays. Green back-lit 4operation keys.
Communication
RS-485 interface port support, 32(128) Networking, ModBus-RTUcommunication protocol.
Energy Pulse (Optional)
One active energy pulse output
Pulse constant: 5000kWh
Photocoupler output (0.1A*30V).
RTC
Accuracy drift less than 2.5min/year
Connection Mode
3P4W, 3P4W BAL, 3P3W, 3P3W BAL, 1P2W, 1P3W.
Programmable
Measuring System : 3P4W/3P3W etc.
Transformation Ratio : PT,CT.
Communication:
Address: 1~247; Baud: 1200~19200; Parity Bit: N/E/O
RTC: Year; Month; Day; Hour; Minute; Second
Energy:Reset
Dimension
Mounting Panel:120X120mm
Thickness:21mm
Depth:118mm
Mounting
Panel Mounting
Trepanning:92X92mm
Power Supply (AC/DC)
AC85~265V / DC85~330V, DC18~90V (optional)
Power Consumption: <4VA
Working condition
Temperature: -25 ~ 55 °C
Humidity: 20% ~ 95%RH, Without condensation
Certifications