Home ProductsCurrent Transformer

110kv High voltage current transformer

Certification
Good quality Current Transformer for sales
I'm Online Chat Now

110kv High voltage current transformer

China 110kv High voltage current transformer supplier

Large Image :  110kv High voltage current transformer

Product Details:

Place of Origin: Beijing, China
Brand Name: GFUVE
Certification: ISO 9001 : 2008; CE
Model Number: GFLVQB6-110

Payment & Shipping Terms:

Minimum Order Quantity: 1SET
Price: USD6000-12000
Packaging Details: Standard export box
Delivery Time: whitin 20 days
Payment Terms: T/T, Western Union, Paypal
Supply Ability: 200pcs/month
Contact Now
Detailed Product Description
Usage: Current Phase: Single
Coil Structure: Toroidal Coil Number: Autotransformer

GFLVQB6-110 outdoor SF6 gas insulation current transformer

Technical parameters  
Rated voltage 110KV
Hightest voltage for equipment 126KV
Rated frequency 50 or 60Hz
Rate transformation ratio 2×200-2×3000/5 or 1A
Number of secondary windings  1-6
Accuracy of measuring winding 0.2,0.2S ,0.5,0.5S
Accuracy of protection winding 5P or 10P
Rated secondary output 20-50 VA
Accuracy limit factors 15,20,25,30
Instrument security factor ≤5 or 10
110kv High voltage current transformer Partial discharge. Under 1.2Um/ ≤5PC
Gas pressure 0.4Mpa
Complementary gas pressure 0.35Mpa
Extermal insulation creepage distance(mm) W1/2750 mm, W2/3150 mm, W3/3900 mm
Power frequency withstand voltage on primary windings 185(230)KVrms
Rated lightming impulse withstand voltage 450(550)KVpeak
Power frequency withstand voltage between primaty section 3KVrms
Power frequency withstand voltage on earth screen to earth  5KVrms
Power frequency withstand voltage on secondary windings and secondary windings to earth 3KVrms
Secondary winding inter-turn withstand viltage 4.5KVpeak
Mechanical strength(three direction) 2500N
Technical parameters  
Rated voltage 110KV
Hightest voltage for equipment 126KV
Rated frequency 50 or 60Hz
Rate transformation ratio 2×200-2×3000/5 or 1A
Number of secondary windings  1-6
Accuracy of measuring winding 0.2,0.2S ,0.5,0.5S
Accuracy of protection winding 5P or 10P
Rated secondary output 20-50 VA
Accuracy limit factors 15,20,25,30
Instrument security factor ≤5 or 10
110kv High voltage current transformer Partial discharge. Under 1.2Um/ ≤5PC
Gas pressure 0.4Mpa
Complementary gas pressure 0.35Mpa
Extermal insulation creepage distance(mm) W1/2750 mm, W2/3150 mm, W3/3900 mm
Power frequency withstand voltage on primary windings 185(230)KVrms
Rated lightming impulse withstand voltage 450(550)KVpeak
Power frequency withstand voltage between primaty section 3KVrms
Power frequency withstand voltage on earth screen to earth  5KVrms
Power frequency withstand voltage on secondary windings and secondary windings to earth 3KVrms
Secondary winding inter-turn withstand viltage 4.5KVpeak
Mechanical strength(three direction) 2500N
Rated primary current Rated short-time current Rated dynamic current
(A) (kA) (kA)
200-400 50(3) 125
300-600 50(3) 125
400-800 50(3) 125
600-1200 50(3) 125
750-1500 63(3) 140
800-1600 63(3) 140
1000-2000 63(3) 140
2000-4000 63(3) 140
3000-6000 63(3) 140

 

Contact Details