Product Details:
Payment & Shipping Terms:
|
FQ-RCTA03: | Flexible AC Current Probe | Operating Temperature & Humidity: | 0 To 50°C (32-122°F), ≤80%RH(No Condensate) |
---|---|---|---|
Storage Temperature & Humidity: | -10 To 60°C (14-140°F), ≤80%RH(No Condensate) | Opera�ng Environment: | Indoor, Altitude Up To 2000 Meters |
Standards Safety: | IEC61010-1:2001, 600V CAT III | Current Range: | 60A/600A/6000A (10%~100%In) |
Output Sensitivity: | 50mV/A, 5mV/A, 0.5mV/A | Accuracy: | ±1%(10%~100%In) @45-65Hz |
Linearity Error: | ±0.2%(10%~100%In) | External Influence: | ±1% Max(More Than 200mm From The Coil) |
Frequency Range: | 10Hz To 20KHz(-3dB) |
COMPANY PROFILE
Beijing GFUVE Electronics Co., Ltd. was established in 2005. It combined science, industry and trade together as one high-tech enterprise. GFUVE mainly produces high voltage ammeter recorder, IEC61850 test suite software, meter test equipment, reference standard meter, phantom load power source, electrical measurement instrument, relay test set, transformer test, and power analyzer, intelligent digital meter, transducer and current transformer models etc.
GFUVE is a leader manufacturer of energy meter test products and high voltage ammeter recorder in China. It is professional in energy meter test system, energy meter portable tester and related accessory. The product of high voltage ammeter recorder develops very quickly in the market. Our company has achieved certification to ISO9001. The products are sold to over 30 provinces in China and exported to overseas including South America, Middle East, Southeast Asia and Africa.
We have been contributing ourselves to developing the durable and stable products for the usage of the power system. Contact us now for further business relationship. We are here to provide you the best service.
PRODUCT INTRODUCTION
The FQ-RCTA03 Flexible AC current probe is designed for easy installed in tight spaces and without the need for dismantling the primary busbar or cables. It includes a flexible Rogowski coil probe and electronic modules. The signal from the coil probe can be amplified by the electronic modules through the integration processing. The output signal can be directly used in oscilloscope, digital multimeter or data logger recording instrument.
Electrical parameters (FQ-RCTA03-305) | |
---|---|
Current range | 60A/600A/6000A (10%~100%In) |
Output sensitivity | 50mV/A, 5mV/A, 0.5mV/A |
Accuracy | ±1%(10%~100%In) @45-65Hz |
Phase error | ±1°(10%~100%In) @45-65Hz 10°@ 20kHz |
Linearity error | ±0.2%(10%~100%In) |
Position Sensitivity | ±2%(The distance from the measured Cable to the junction is above 20mm) |
External Influence | ±1% Max(More than 200mm from the coil) |
Noise | 8mV rms(60A); 2 mV rms (60A) |
Temperature coefficient | ±0.08%/°C of the reading data |
Frequency Range | 10Hz to 20Hz(-3dB) |
Load impedance | Min 100KΩ |
Power supply | 2*AA|MN1500|LR6 Batter y(400 hrs) External adapter: 4.5V DC |
Power LED Indicator | ON indication When normal power (Red light goes off after 3 seconds) Low batter y indication(Red is always on) |
Overload LED indicator | Overload above 120% of the range indication(Yellow) |
Operating voltage | 600V AC RMS or DC |
Security level | IEC61010-1:2001,600V CAT III |
Mechanical parameters | |
Cable length | 3m (Measuring head to the electronics module) |
Output terminals | 0.5m cable with Safety BNC plug |
Weight | 230g (Measuring head),130g (Electronic modules) |