Product Details:
Payment & Shipping Terms:
|
Names: | Programmable Multi-function Power Source | Accuracy: | 0.05% |
---|---|---|---|
Current Range: | 0-24A Ac/dc | Voltage Range: | 0-1050V Ac/dc |
Resistance: | 0-10MΩ | Frequency: | 45-65Hz |
Weight: | 12KG | Clamp Meter: | 0-1000A |
Standard: | ISO17025 | Power Supply: | 220V AC 50/60Hz |
GF6018A 1000A 20A AC DC portable programmable multi-function power source
The test equipment of Portable mulifunction calibrator with voltage source and current source is compliance with national verification regulation: JJG124-2005 “Ammeter, voltmeter, power meter and resistance meter verification rules” and related national standards. 0.05 single-phase AC/DC standard source, can verify magnitude 0.2 and the following AC/DC voltmeter, ammeter, frequency meter, resistance meter. The source signals by using DSP and 16-bit high-speed analog-to-digital converters of controllable sine wave, the distorted wave signal source.The equipment comes with RS-232 interface, can be connected with PC to a semi-automatic verification system. It has precise interface and multi-functions including verification, storage and query.The equipment adopts color LCD screen, chart character display is clear, with high precision, stable and reliable, convenient operation and flexible characteristics.
GF6018A programmable multi-function power source is an intelligent power standards developed in 2008. Featured with high stability, easy operation, it is an ideal upgraded product for calibration of “AC/DC voltmeter, AC/DC current meter, frequency meter, phase meter, AC/DC power meter and electrical quantity transducer”. The multi-function power source is characterized by phase angle closed loop, voltage closed loop, current closed loop so as to ensure low shift and year stability. Besides, it is equipped with full duplex RS232 interface and GPIB interface which in compliance with IEEE standard 488.2 for easy connection with PC, suitable for auto test system.
Electrical parameters | ||
---|---|---|
Power supply | Single phase AC 220V±10% or 110V±10%, 50/60HzAC | |
AC Voltage output | ||
range | 200mV, 400mV, 2000mV, 4000mV, 20V, 100V, 200V, 500V, 1000V |
|
Range 20V-1000V | Accuracy | ±(0.03%RD+0.02%FS) |
Stability | ≤0.01% FS /60s | |
Range 200mV-4000mV | Accuracy | ±(0.3%RD+0.2%FS) |
Stability | ≤0.04% FS /60s | |
Load capacity | 20VA | |
Waveform distortion | ≤0.3% | |
Adjustable Range | 0-120% FS (1000V not included) | |
Fineness | 5×10-5 | |
AC Current Output | ||
Range | 2mA, 4mA, 20mA, 40mA, 0.2A, 0.5A, 2A, 5A, 10A, 20A | |
Range 0.2A-20A | Accuracy | ±(0.03%RD+0.02%FS) |
Stability | ≤0.01% FS /60s | |
Range 2mA-40mA | Accuracy | ±(0.3%RD+0.2%FS) |
Stability | ≤0.04% FS /60s | |
Load capacity | 20VA | |
Waveform distortion | ≤0.3% | |
Adjustable Range | 0-120% FS | |
Fineness | 5×10-5 | |
Frequency Output | ||
Range | 45-65Hz | |
Fineness | 0.001Hz | |
Accuracy | 0.01Hz | |
Harmonic Wave | ||
Times | 2-31 | |
Extent | 0-20% | |
Each harmonic phase fineness | 0.01·N (N is harmonic order) | |
DC voltage output | ||
Range | 200mV, 400mV, 2000mV, 4000mV, 20V, 40V, 100V, 200V, 400V, 1000V |
|
Load capacity | 20W | |
Adjustable range | 0-110% FS (1000V not included) | |
Adjustable fineness | 5×10-5 | |
Stability | ≤0.01% FS /60s (peak-peak value) | |
Accuracy | ±(0.03%RD+0.02%FS) | |
Ripple wave | ≤1% FS | |
DC current output | ||
Range | 20uA, 40uA, 200uA, 400uA, 2mA, 4mA, 20mA, 40mA, 0.2A, 1A, 2.5A, 5A, 10A, 20A |
|
Load capacity | 20W | |
Adjustable Range | 0-110% FS (1000V not included) | |
Adjustable Fineness | 5×10-5 | |
Stability | ≤0.01% FS /60s (peak-peak value) | |
Accuracy | ±(0.06%RD+0.04%FS) | |
Ripple wave | ≤1% FS | |
Resistance box | ||
Range | 0-200Ω, 200-400Ω, 0-2kΩ, 2kΩ-4kΩ, 0-20kΩ, 20kΩ-40kΩ, 0-200kΩ, 200kΩ-400kΩ, 0-2MΩ, 2MΩ-4MΩ |
|
Fineness | 0.02% | |
Range 0-2kΩ, 0-20kΩ, 0-200kΩ | ||
Range 0-2kΩ | Adjustable Range | 0-100%FS |
Accuracy | ±(0.12%RD+0.08%FS) | |
Range 0-200Ω,0-2MΩ | Adjustable Range | 0-100% FS |
Accuracy | ±(0.3%RD+0.2%FS) | |
Range 2kΩ-4kΩ, 20kΩ-40kΩ, 200kΩ-400kΩ | ||
Range 2kΩ-4kΩ | Adjustable Range | 5%-100%FS |
Accuracy | ±(0.12%RD+0.08%FS) | |
Range 200-400Ω, 2MΩ-4MΩ |
Adjustable Range | 5%-100% FS |
Accuracy | ±(0.3%RD+0.2%FS) | |
Clamp meter range | ||
200A | Accuracy | ±0.2% |
600A | Accuracy | ±0.5% |
1000A | Accuracy | ±1% |
Dot frequency square wave output | ||
Range | 1kHz, 5kHz, 10kHz, 50kHz, 100kHz, 200kHz, 1000kHz | |
Square wave amplitude | 4.5V | |
Setting accuracy | 5×10-5 | |
Mechanical parameters | ||
Dimension (L×W×H) (mm) | 440x360x160 | |
Weight (kg) | 12 | |
Environmental conditions | ||
Operating temperature | 20°C±10°C | |
Relative humidity | ≤85%RH |
http://gfuve.com/electrical-calibration/clamp-type-multimeter-calibrator.html