Product Details:
Payment & Shipping Terms:
|
| Usage: | Magnetic Sensor | Theory: | Current Sensor |
|---|---|---|---|
| Output: | Analog Sensor |
The FQ-RCT02 Flexible AC current probe are designed for easy installed in tight spaces and without the need for dismantling the primary busbar or cables.
| Electrical parameters | |||||||
|---|---|---|---|---|---|---|---|
| Model | FQ-RCT02-120 | FQ-RCT02-190 | FQ-RCT02-305 | FQ-RCTA02-120 | FQ-RCTA02-190 | FQ-RCTA02-305 | |
| Current range | 10A~30kA | 10A~6000A | |||||
| Frequency | 25Hz~20kHz | 45Hz~600Hz | |||||
| Output voltage | Rated current | 1000A | 2000A | 3000A | 250A, 500A, 800A, 1000A | 1000A, 1500A, 2000A, 2500A | 1000A, 2000A, 2500A, 3000A |
| 50Hz | 100mV AC | 200mV AC | 300mV AC | ||||
|
333mV 1mV/A@1000-3000A(0.5mV/A@4000-6000A) |
|||||||
| Max output | / | 3.0V AC max | |||||
| Accuracy | <1% @25°C (45-65Hz) | <1% @25°C (45-65Hz) | |||||
| Phase error | <60’ @25°C (45-65Hz) | <60’ @25°C (45-65Hz) | |||||
| Output sensitivity |
±2% Max (No Calibration) ±0.5% @25°C (With Calibration) |
1% | |||||
| Linearity error | ±0.2% (10%-100%I1n) | ±0.2% | |||||
| Position sensitivity | ±2% | ±2% | |||||
| External influence | ±2% Max | ±1.5% Max | |||||
| Power supply | / | 10-30VDC,30mA Max. | |||||