Product Details:
Payment & Shipping Terms:
|
Measuring Current Range: | 0-10A | Measuring Voltage Range: | 0-500V |
---|---|---|---|
Accuracy Class: | 0.5% | Operating Temperature: | -40~+70°C |
Dimensions: | 110mm X 75mm X 120mm |
FUD-Type-Input-Power Supply-Output | ||||
---|---|---|---|---|
Type |
P3: 3P3W active power transducer Q3: 3P3W reactive power transducer PQ3: 3P3W active and reactive power transducer |
|||
AC input |
V1: 100V, V2: 0-220V, V3: 270V, V4: 400V A1: 0-1A, A2: 0-5A. |
|||
Power supply | P1: AC110V±10%, P2: AC220V±15%, P3: AC110V-330V. | |||
DC output |
O1: 0-20mA, O2: 0-±20mA, O3: 4-20mA, O4: 4-12-20mA, O5: 0-1V, O6: 0-±1V, O7: 0-5V, O8: 0-±5V, O9: RS485. |
|||
Example 1: FUD-P3-V1-A2-P2-O8 | ||||
FUD series 3P3W active power transducer | Input: AC100V, ±5A , ±866W | |||
Power supply: AC220V±15% | ||||
Output: DC0-±5V | ||||
Example 2: FUD-PQ3-V1-A2-P2-O8 | ||||
FUD series 3P3W active and reactive power transducer | Input: AC100V, ±5A , ±866W(var) | |||
Power supply: AC220V±15% | ||||
Output: DC0-±5V | ||||
Please check the type, input range, output range and power supply when your order the product. |
Technical Index | |
---|---|
Standard | GB/T 13850-1998, IEC688:1992 |
Accuracy | 0.2%, 0.5% |
Consumption | ≤5VA |
Accuracy drift | Annual variation < 0.2% |
Insulation voltage | AC 2kV/min.1mA (Between input- output / power) |
Insulation resistance | ≥20MΩ (DC500V) |
Surge voltage | 5KV (Peak value), 1.2/50μs |
Response time | ≤350ms |
Input range | AC 0-5A ,AC 0-500V(Option), 50/60Hz |
Absorbed power |
Per phase voltage: ≤0.5VA/100V Per phase current: <0.1VA/5A |
Overload |
Current: 2 times continuous, 30 times /1s; Voltage: 2 times continuous |
Load resistance | Current output: RL≤650Ω |
Voltage output: RL≥2kΩ | |
Working environment | Temperature: -10 to +50℃ |
RH: 20-90%, without condensation | |
Storage conditions | Temperature: -40 to +70℃ |
RH: 20-95%, without condensation | |
Installation | 35mm DIN sliding-way or M4 screws |
Dimension | 110mm x 75mm x 120mm |