Home ProductsCT Analyzer

PRECISION TRANSFORMER TESTING PORTABLE CT PT ANALYZER

Certification
Good quality Current Transformer for sales
I'm Online Chat Now

PRECISION TRANSFORMER TESTING PORTABLE CT PT ANALYZER

China PRECISION TRANSFORMER TESTING PORTABLE CT PT ANALYZER supplier

Large Image :  PRECISION TRANSFORMER TESTING PORTABLE CT PT ANALYZER

Product Details:

Place of Origin: Beijing, China
Brand Name: GFUVE
Certification: ISO 9001 : 2008; CE
Model Number: GF1061

Payment & Shipping Terms:

Minimum Order Quantity: 1SET
Price: USD20000-35000
Packaging Details: Standard export box
Delivery Time: 7days
Payment Terms: T/T, Western Union, Paypal
Supply Ability: 200pcs/month
Contact Now
Detailed Product Description
Power: Electronic Usage: Auto Testing Machine
Accuracy: 0.05% Types: PORTABLE CT PT ANALYZER

GF1061 PRECISION TRANSFORMER TESTING PORTABLE CT PT ANALYZER

GF1061 portable CT PT analyzer is mainly used for field or lab testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt 7 inch touch TFT LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The CT PT Analyzer is the most complete and easy-to-use testing system for protection and metering CTs according to IEEE and IEC standards.

MAIN FUNCTIONS

I. Current Transformer (CT) II. Voltage Transformer (PT)
1. Magnetization curve 1. Excitation characteristic test
2. Transformation ratio test 2. Transformation ratio test
3. Polarity 3. Polarity 
4. 5% and 10% error curve 4.  Ratio error, phase error
5. Accuracy limiting factor (ALF) 5. Degauss
6. Degauss 6. Calculation of knee point value
7. Ratio error, phase error 7. Actual secondary load test (burden test)
8. Automatic calculation of excitation knee 
point value
8. Resistance test
9. Actual secondary load test (burden test)
10. Resistance test 
11. Secondary time constant (Ts)
12. Remanence coefficient (Kr)
13. Transient dimensioning factor (Ktd)
14. Peak instantaneous error (Er)
15. Magnetizing inductance (LU)
16. Instruments security factor(FS)
17. Composite error

PARAMETERS

Electrical parameters
Accuracy 0.05%
Power supply AC 220V±10% or AC 120V±10%, 50/60Hz or Battery
Output voltage 0-100Vrms
Output current 0-5Arms (20A peak-value)
Output power 0-400 VA (1500 VApeak)
Automatic frequency variation range 0.1-60Hz
Equivalent excitation voltage ≤5000V
Accuracy ≤0.5%
Secondary winding DC resistance measurement Range 0.1-1000Ω
Accuracy ≤0.05%
Secondary actual load measurement Range 5VA-1000VA
Accuracy ≤0.5%±0.1VA
CT/PT phase error measurement Accuracy ±1min (typical) / 3 min (guaranteed)
Resolution 0.1min
CT ratio error measurement Range 1-50000
Accuracy ≤0.05%
PT ratio error measurement Range 1-10000
Accuracy ≤0.05%
Standards 
Reference standards GB1207-2006, GB1208-2006, GB16847-1997 
IEC60044-1, IEC60044-6, IEC61869-2, ANSI/IEEE C57.13
Safety standards GB 4793.1-2007
EMC EMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2 /3 /4 /6
Mechanical parameters 
Overall dimension (L x W x H) (mm) 280 x 250 x 160
Weight (kg)   ≤4
Environmental conditions 
Relative humidity    Relative humidity 5%-95% not condensing
Operating temperature -10°C to +50°C
Storage temperature -20°C to +70°C
Altitude ≤1000m

 

Contact Details
Beijing GFUVE Electronics Co.,Ltd.

Contact Person: Mr. Andy

Tel: 86-10-85782698

Fax: 86-010-85781298

Send your inquiry directly to us (0 / 3000)